Technical details
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Measuring accuracy
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Warm up time
approx. 1 hour
Service life
> 60 months (under normal load conditions)
depending on the type of loading and gas concentration
Response time
< 2 minutes
Output, CO2
0 -10 V or 4...20 mA (selectable via DIP switches)
Ambient temperature
0...+50 °C
Electrical connection
0.14 - 1.5 mm² via terminal screws
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Relay output
with potential-free changeover contact 24 V (assignment selectable via DIP switches)
Output
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches)
with offset potentiometer (± 10 % of the measuring range
Sensor
Optical NDIR sensor (non-dispersive infra-red technology),
with manual calibration (via zero button),
with automatic calibration (can be deactivated via DIP switches)
Measuring range
0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions
98 x 98 x 33 mm (Baldur 2)
Installation
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Standards
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014/ 30/ EU,
Low Voltage Directive 2014/ 35/ EU
Display
with display for displaying the actual CO2 content in ppm