Surface contact / tube contact temperature measuring transducer
THERMASGARD® ALTM1
Calibratable THERMASGARD® ALTM 1 surface-contact temperature measuring transducer (compact version) with eight switchable measuring ranges, continuous output, in an impact resistant plastic housing with quick-locking screws, optionally with/without display, incl. strap.
The surface-contact sensor serves to detect the temperature on lines, pipes (e.g. cold and warm water) or on heating sections for heating control. The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
Technical details
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
< 2,2 VA/ 24 V AC
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
depending on working resistance, residual ripple stabilised ± 0.3 V
Temperature deviation
typically ± 0.2 K at +25 °C
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Sensor
Pt1000, DIN EN 60751, class B
Connection type
2- or 3-wire connection
Ambient temperature
Measuring transducer –30...+70 °C
Process connection
endless metal strap and metal tightener
(included in scope of delivery)
(included in scope of delivery)
Insulating resistance
100 MΩ,
at +20 °C (500V DC)
at +20 °C (500V DC)
Strap dimensions
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
Electrical connection
0.14 - 1.5 mm² via terminal screws
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
max. inner diameter 10.4 mm
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Output
4...20 mA
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
(other ranges optional)
compact variant: Tmax up to 100 °C, operating range –50...+100 °C
with manual zero point correction (± 10 K)
(other ranges optional)
compact variant: Tmax up to 100 °C, operating range –50...+100 °C
with manual zero point correction (± 10 K)
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions
72 x 64 x 37,8 mm (Tyr 1)
Protection type
IP 65 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No.713139052 (Tyr 1)
TÜV SÜD, Report No.713139052 (Tyr 1)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU