Surface contact temperature/ tube contact temperature measuring transducers ALTM1-Modbus-T3
temperature Temperature

Surface contact temperature/ tube contact temperature measuring transducers THERMASGARD® ALTM1-Modbus-T3

Item no. 1101-12B6-0000-000
EAN 4251325618616
Product group: WG01

In Stock

Usually ships in 1 to 3 days
177,19 €
210,86 € incl. VAT + shipping
+

Description

Surface contact temperature/ tube contact temperature measuring transducers THERMASGARD® ALTM1 - Modbus - T3
Calibratable surface-contact temperature measuring transducer (compact variant) THERMASGARD® ALTM 1 - Modbus - T3 with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, pipe feeder, incl. strap, optionally with/ without display, measures temperature (–50...+150 °C). International system of units SI (default) can be changed to imperial (via Modbus).

The pipe surface-contact sensor is used to detect the temperature on lines, pipes (e.g., cold and warm water) or on heating sections for heating control.
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated, with customised programming in the 7-segment range and dot-matrix range). Uses internal diagnostics to detect sensor breakage or sensor short circuit as errors. The error messages can be retrieved via Modbus and are shown on the display. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Measuring range, temperature
–50...+150 °C
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B
Measuring range
–50...+150 °C
Tmax up to +100 °C (compact variant)
Zero point offset
± 10 °C
Ambient temperature
Measuring transducer –30...+70 °C
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Process connection
endless metal strap and metal tightener
(included in scope of delivery)
Communication
Modbus RTU (RS485 interface for RTU cable)
Strap dimensions
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Internal diagnostics
Error 1 at sensor breakage
Error 2 at sensor short circuit
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions
108 x 78.5 x 43.3 mm (Tyr 3 without display)
Cable gland
2x M 20 x 1.5; with strain relief, replaceable,
inner diameter 8 - 13mm
Standards
CE conformity according to EMC Directive 2014 / 30 /EU

Accessories