Room humidity, temperature and CO2 sensor or measuring transducer FSFTM-CO2-Modbus
temperature Temperature
temperature Luftfeuchtigkeit
temperature CO2

Room humidity, temperature and CO2 sensor or measuring transducer AERASGARD® FSFTM-CO2-Modbus

Item no. 1501-9226-6001-162
EAN 4251325617299
Product group: WG02

In Stock

Usually ships in 1 to 3 days
385,89 €
459,21 € incl. VAT + shipping
+

Description

Room humidity, temperature and CO2 sensor or measuring transducer AERASGARD® FSFTM-CO2 - Modbus
TheAERASGARD® FSFTM - CO2 - Modbus room sensor and measuring transducer with in-wall housing and optional potentiometer is used to measure The CO2 content, relative humidity and temperature of the air, and for setpoint adjustment. The measured values are queried via the Modbus interface.

The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra- red technology). A digital, long-term stable sensor is used for humidity and temperature measurement. Relative humidity [% r.H.] is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature.


The in-wall transmitter is mounted either individually or in combination with light switches, socket outlets, etc. in high-quality panel switch brand programmes, such as preferably from Gira, Berker, Merten, Jung, Siemens or Busch-Jaeger (with in-wall adapters, no setpoint adjustment possible).
It is used in non-aggressive, dust-free environments, in refrigeration, air conditioning and cleanroom engineering, and in interior spaces, such as living rooms, offices, hotels, etc.

Technical details

Data points
temperature, relative humidity, carbon dioxide (CO2)
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 4.4 W/ 24 V DC typical; < 6.4 VA/ 24 V AC typical;
peak current 200 mA
Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % RH (without dew formation)
Deviation of humidity
typically ± 3.0 % (20...80 % r. H.) at +25 °C, otherwise ± 5.0 %
Measuring range, temperature
0...+50 °C
Temperature deviation
typically ± 0.8 K at +25 °C
Warm up time
approx. 1 hour
Response time
< 2 minutes
Long-term stability
< 2 % in 15 years

± 1 % per year
Protection class
III (according to EN 60 730)
Protection type
IP 20 (according to EN 60 529)
Protection type housing
IP 20
Measuring range, CO2
0...5000 ppm
Sensor, CO2
optical NDIR sensor
(non-dispersive infra-red technology),
with manual calibration (via zero button) and
automatic calibration (fixed)
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Measuring range
0...5000 ppm
Ambient temperature
storage –35...+85 °C;
operation 0...+50 °C
Medium
clean air and
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
4 s / 32 s
Electrical connection
0.14 - 1.5 mm², using plug terminals
Housing
plastic, colour pure white glossy (similar to RAL 9010)
(other colours are possible on request with colour variants
depending on the respective switch programme)
Installation
in in-wall flush box Ø 55 mm
Permissible air humidity
max. 90 % RH, non-precipitating air
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Manufacturer
GIRA System 55 Standard
(other switch programmes, manufacturers, colours