Pendulum room humidity and temperature sensors RPFTF-wModbus LCD
new
temperature Temperature
temperature Luftfeuchtigkeit

WIRELESS Pendulum room humidity and temperature sensors HYGRASGARD® RPFTF-wModbus LCD

Item no. 1201-624F-1400-000
EAN 4251325628370
Product group: WG01

Low availability.

Usually ships in 3 to 5 days
432,80 €
515,03 € incl. VAT + shipping
+

Description

Pendulum room humidity and temperature sensors HYGRASGARD® RPFTF - Modbus - T3
W-Modbus is a wireless-based further development of the proven Modbus standard for the wireless connection of Modbus-enabled sensors, controllers and devices. W-Modbus devices communicate via a wireless radio link from LumenRadio - independently of the in-house Wi-Fi and without leaving the proven protocol standards. Thanks to the reliable and interference-resistant wireless network, entire buildings can be networked and the majority of Modbus RTU cables can be replaced.
Innovative Modbus sensor with galvanically separated RS485-Modbus-interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in curentfree state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Data points
Temperature [°C], relative humidity [% RH],
dew point [°C], absolute humidity [g / m3],
mixture ratio [g / kg], enthalpy [kJ / kg]
Measuring range, humidity
0...100 % RH
Measuring range, temperature
–35...+180 °C
Temperature deviation
typically ± 0.2 K at +25 °C
Measuring ranges
0...100 % RH (humidity)
-35...+80 °C (temperature)
Zero point offset
± 10 % RH (humidity)
± 5 °C (temperature)
Ambient temperature
–30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
4 s / 32 s
Protective tube
stainless steelV2A (1.4301), Ø = 16 mm, L = 142 mm
Communication
W-Modbus (Wireless Modbus with 2.4 GHz ISM)
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Cable gland
2x M 20 x 1.5; with strain relief, replaceable,
inner diameter 8 - 13mm
sensor cable
PVC, LiYY, 6 x 0.14 mm²,
KL = approx. 2 m (other lengths optional)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Units
switchable metric / imperial
Standards
CE conformity,
electromagnetic compatibility according to EN 61326, ETSI 300 328
according to EMC Directive 2014/ 30/ EU, Radio Directive 2014 / 53 / EU