Air flow monitor PLSW-W24
new
temperature Strömung

Air flow monitor RHEASREG® PLSW-W24

Item no. 1701-6113-0101-001
Product group: WG01

Low availability.

Usually ships in 3 to 5 days
213,06 €
253,54 € incl. VAT + shipping
+

Description

Air flow monitor RHEASREG® PLSW-W24
Electronic pendulum airflow sensor RHEASGARD® PLGF with active output, housing made of impact-resistant plastic with quick-locking screws, with cable gland, with/without display, with external duct probe incl. mounting flange, to determine the flow velocity (0.1...20 m/s). The measuring transducer converts the measurement signal into a standard signal of 0 - 10 V.

Electronic pendulum airflow sensor/monitor RHEASGARD® PLGFT (without display) and PLGFVT (with display) with active and switching output, housing made of impact-resistant plastic with quick-locking screws, with cable gland, with external duct probe incl. mounting flange, to determine the flow velocity (0.1...20 m/s) and temperature (0...+50 °C). For unit type PLGFVT, the calculated volume flow parameter can be retrieved as an alternative to the flow (configurable on the display). The measuring transducer automatically detects the required output type and converts the measurands into the required standard signal of 0 - 10 V or 4...20 mA (Automatic Output Switching).

Electronic pendulum airflow monitor RHEASREG® PLSW with switching output, housing made of impact-resistant plastic with quick-locking screws, with cable gland, with/without display, with external duct probe incl. mounting flange, to determine the flow velocity (0.1...20 m/s).
The flow sensors are suitable for monitoring or controlling airflows in ducts, at fans and dampers, for flow-dependent monitoring of humidifiers and electric heating registers according to DIN 57100, Sect. 420, or for use in connection with DDC systems.

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Data points
flow velocity
Start bridging
0 / 60 s (can be activated via DIP switch)
Measuring accuracy
0,5 m/s + 3 % MW
Warm up time
< 2 min
Response time
< 5 s
Output
0-10 V (linearized)
Output
0-10 V
Output signal
linearized
Sensor
calorimetric, temperature compensated, sensor breakage protection, with manual zero point calibration (via push button)
Current consumption
approx. 3 VA
Measuring range
0,1...20 m/s
Media temperature
0…+70 °C
Ambient temperature
storage –20...+ 50 °C
operation 0...+ 50 °C
Medium
pollutant-free, non-precipitating air
Process connection
by means of mounting flange with seal (included in the scope of delivery)
Protective tube
Polyamide (PA6) material, white colour (blue sensor holder), with torsion protection, Ø 12 mm, EL = approx. 20–155 mm, vmax = 30 m/s (air)
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable connection
Cable fitting, plastic
(M 16 x 1.5; with strain relief, exchangeable,
max. inner diameter 10.4 mm)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Dimensions
126 x 90 x 50 mm (Tyr 2)
sensor cable
PVC LiYY, 5-wire, KL = approx. 2.4 m
Installation
On-wall housing with external duct probe – observe flow direction!
Long-term stability
± 0.5 % of final value per year
Permissible air humidity
< 98 % RH, non-precipitating air free of harmful substances
Protection class
III (according to EN 60 730) where UB = 24 V
Protection type
IP65, Sensors IP 20
Protection type (sensor)
IP20
Protection type housing
IP 65 (according to EN 60 529)*
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
Optional
display with illumination, three-line, cutout approx. 70 x 40 mm (W x H), to indicate the flow velocity, volume flow and temperature
Reproducibility
± 1,0 % EW