temperature Strömung

Air flow monitor RHEASREG® PLSW-W24

Item no. 1701-6113-0101-001
Product group: WG01

Low availability.

Usually ships in 3 to 5 days
213,06 €
253,54 € incl. VAT + shipping
+

Description

Air flow monitor RHEASREG® PLSW-W24
Electronic pendulum airflow monitor RHEASREG® PLSW with switching output, housing made of impact-resistant plastic with quick-locking screws, with cable gland, with/without display, with external duct probe incl. mounting flange, to determine the flow velocity (0.1...20 m/s).
The flow sensors are suitable for monitoring or controlling airflows in ducts, at fans and dampers, for flow-dependent monitoring of humidifiers and electric heating registers according to DIN 57100, Sect. 420, or for use in connection with DDC systems.

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Switchpoint
1...20 m/s, threshold can be adjusted via potentiometer
Data points
flow velocity
Start bridging
0 / 60 s (can be activated via DIP switch)
Measuring accuracy
0,5 m/s + 3 % MW
Warm up time
< 2 min
Response time
< 5 s
Output
Changeover contact (24 V)
Sensor
calorimetric, temperature compensated, sensor breakage protection, with manual zero point calibration (via push button)
Current consumption
approx. 3 VA
Measuring range
0,1...20 m/s
Media temperature
0…+70 °C
Ambient temperature
storage –20...+ 50 °C
operation 0...+ 50 °C
Medium
pollutant-free, non-precipitating air
Switching hysteresis
2.0 % of final value
Process connection
by means of mounting flange with seal (included in the scope of delivery)
Protective tube
Polyamide (PA6) material, white colour (blue sensor holder), with torsion protection, Ø 12 mm, EL = approx. 20–155 mm, vmax = 30 m/s (air)
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable connection
Cable fitting, plastic
(M 16 x 1.5; with strain relief, exchangeable,
max. inner diameter 10.4 mm)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Dimensions
126 x 90 x 50 mm (Tyr 2)
sensor cable
PVC LiYY, 5-wire, KL = approx. 2.4 m
Installation
On-wall housing with external duct probe – observe flow direction!
Long-term stability
± 0.5 % of final value per year
Permissible air humidity
< 98 % RH, non-precipitating air free of harmful substances
Protection class
III (according to EN 60 730) where UB = 24 V
Protection type (sensor)
IP20
Protection type housing
IP 65 (according to EN 60 529)*
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
Optional
display with illumination, cutout approx. 70 x 40 mm (W x H)
Reproducibility
± 1,0 % EW