Duct air quality sensors/ controllers (VOC) KLQ-W
temperature VOC

Duct air quality sensors/ controllers (VOC) AERASGARD® KLQ-W

Item no. 1501-3150-7301-500
EAN 4251325624297
Product group: WG02

In Stock

Usually ships in 1 to 3 days
228,48 €
271,89 € incl. VAT + shipping
+

Description

Duct air quality sensors/ controllers (VOC) AERASGARD® KLQ-W
Patented quality product (patent no. DE 10 2014 010 719.1)
Maintenance-free AERASGARD® KLQ-SD duct air quality measuring transducer with active output, automatic calibration, in a compact plastic housing with snap-on cover, for determining the air quality (0…100% VOC). The transmitter converts the measured values into a standard signal of 0-10 V.
Maintenance-free AERASGARD® KLQ-W durct air quality measuring transducer with active/switching output, automatic calibration, in a compact plastic housing with quick-locking screws, for determining the air quality (0…100% VOC). The transmitter converts the measured values into a standard signal of 0-10 V or 4...20 mA (switchable).
The sensor device is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating
costs and improving well-being.
The air quality is detected by a VOC sensor (mixed gas sensor for volatile organic substances). This sensor determines the load of contaminated gases in the room air, such as from cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions etc. With regard to the expected air contamination, low, medium or high VOC sensitivity can be selected. As an alternative, use IAQ categories to assess the room air (from excellent to unhealthy) following the guidelines of the German Federal Environmental Agency.

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Data points
Air quality (VOC)
Measuring range, VOC
0...100 % Air quality - VOC sensitivities (low/medium/high)
Measuring accuracy
± 20 % of final value (referred to calibrating gas)
Gas exchange
by diffusion
Warm up time
approx. 1 hour
Response time
approx. 1 minute,
minimum flow rate 0.2 - 0.5 m/s
Service life
> 60 months (under normal load conditions),
depending on the type of loading and gas concentration
Ambient temperature
–10...+60 °C
Process connection
by mounting flange, plastic
(included in the scope of delivery)
Electrical connection
0.14 - 1.5 mm² via terminal screws
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
Relay output
with potential-free changeover contact (24 V / 1 A),
switchpoint adjustable
Protection class
III (according to EN 60 730)
Output
(0 V = clean air, 10 V = polluted air)
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches)
with offset potentiometer (± 10 % of the measuring range
Sensor
VOC sensor (metal oxide) (VOC = volatile organic compounds),
with manual calibration (via zero button),
with automatic calibration (can be deactivated via DIP switches)
Measuring range
0...100 % air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches)
VOC sensitivity low, medium, high
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 202.5 mm, vmax = 30 m/s (air)
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions
72 x 64 x 37,8 mm (Tyr 1)
Protection type
IP 65 (according to EN 60 529)* Housing tested,
TÜV SÜD, Report No. 713139052 (Tyr 1)
Housing in the built-in state
(permeable PLEUROFORM: IP 30)
Protection type housing
IP 65
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU