- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Rymaskon
- Modbus | Wireless Modbus
- EtherCAT P
- Accessory
Description
Ceiling built-in humidity and temperature sensors
HYGRASGARD® DFTF - Modbus
The calibratable HYGRASGARD® DFTF - Modbus humidity and temperature transmitter measures the relative humidity and temperature of air.
Relative humidity (in % RH) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature. The sensor device provides precise detection of temperature and humidity. A digital, long-term stable sensor serves as measuring element for humidity and temperature. Fine adjustment by the user is possible.
Relative humidity (in % RH) is the quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature. The sensor device provides precise detection of temperature and humidity. A digital, long-term stable sensor serves as measuring element for humidity and temperature. Fine adjustment by the user is possible.
The sensor has been designed for use in non-aggressive, dust-free environments and can be installed in suspended ceilings of corridors, offices, as well as residential and commercial buildings. The connecting head is pluggable for quick, easy mounting. The measuring transducer is accommodated in a separate housing.
Technical details
Power consumption
< 1.1 VA/ 24 V DC ; < 2.2 VA/ 24 V AC
Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % RH (without dew formation)
Deviation of humidity
typical ± 2.0 % (20…80 % RH); at + 25 °C, otherwise ± 3.0 %
Ambient temperature
storage –5...+60 °C
operation –5...+60 °C
operation –5...+60 °C
Electrical connection
0.14 - 1.5 mm²
via terminal screws on circuit board
via terminal screws on circuit board
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 10.4 mm
max. inner diameter 10.4 mm
sensor cable
PVC, LiYY, 4 x 0.14 mm²,
KL = approx. 2 m
KL = approx. 2 m
Long-term stability
± 1 % per year
Mounting (sensor)
inside suspended ceiling,
ceiling cutout Ø = 30 mm,
cover Ø = < 35 mm
ceiling cutout Ø = 30 mm,
cover Ø = < 35 mm
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
M12 connector according to DIN EN 61076-2-101 (optional on request)
Protection class
III (according to EN 60 730)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions
72 x 64 x 37,8 mm (Tyr 1)
Connecting head
made of plastic, material polycarbonate (PC), colour white,
pluggable, Ø = approx. 35 mm, H = approx. 29 mm,
with metal sinter filter made of stainless steel V4A (1.4404)
pluggable, Ø = approx. 35 mm, H = approx. 29 mm,
with metal sinter filter made of stainless steel V4A (1.4404)
Protection type
IP 67 (according EN 60 529) Housing tested
TÜV SÜD, Report No. 713139052
IP 30 (according EN 60 529) Sensor in the built-in state
TÜV SÜD, Report No. 713139052
IP 30 (according EN 60 529) Sensor in the built-in state
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3