- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Rymaskon
- EtherCAT P
- Accessory
Description
pendulum CO2 sensor
AERASGARD® RPCO2
The RPCO2 air quality sensor detects the CO2 concentration of the ambient air in the range of 0-10000 ppm via a non-dispersive infrared sensor (NDIR) and converts this measured value into a linear output signal 0-10 V or 4-20 mA. The transmitter is simply suspended as a pendulum in the room, which ensures an accurate measurement result in high rooms.
As an option, the air quality sensor has a potential-free changeover contact and a backlit display. There are 3 different scalings (0-2000 ppm, 0-5000 ppm, 0-10000 ppm) which can be selected via DIP switches.
Zero adjustment in relation to the actual ambient conditions can be performed by manual calibration on the instrument. The air quality sensor performs an automatic self-calibration at regular intervals, ensuring a long-term stable CO2 measurement.
Zero adjustment in relation to the actual ambient conditions can be performed by manual calibration on the instrument. The air quality sensor performs an automatic self-calibration at regular intervals, ensuring a long-term stable CO2 measurement.
Technical details
Voltage supply
24 V AC/DC (± 5 %)
Power consumption
Ø 100mA, peak current up to 300mA
Data points
Carbon dioxide (CO2)
Operating range, humidity
0...98% RH, pollutant-free, non-precipitating air
Measuring range, CO2
multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm; 0...10000 ppm
0...2000 ppm; 0...5000 ppm; 0...10000 ppm
Sensor, CO2
optical NDIR sensor (non-dispersive infra-red technology)
with automatic and manual calibration
with automatic and manual calibration
Measuring accuracy, CO2
± 75ppm ± 5% MW up to 5,000ppm, otherwise ± 100ppm ± 5% MW
@ 68°F, 45% RH, 1013mbar, auto calibration activated
Pressure dependence
0.16% of measured value/hPa Difference to 1013mbar
Warm up time
10 min
Response time
< 5min
Output
0 - 10V/ 4-20mA, 3-wire connection
Measuring range
0...2000 ppm / 0...5000 ppm / 0...10000 ppm
Operating temperature
32...+122 °F
Storage temperature
-4...+122 °F
Connection cable
PVC, 6.56 ft
Protective tube
Ø0.98x 3.15 in
Electrical connection
AWG 16 - 26 via terminal screws
Housing
Polycarbonate with hinge locks
Color signal white (similar to RAL 9003)
Color signal white (similar to RAL 9003)
Cable gland
M 16 x 1.5; including strain relief
Long-term stability
±1% EW/ Year
Protection class
III (according to EN 60 730)
Protection type
IP 65/30 (housing / probe)
Protection type (sensor)
IP 30
Protection type housing
IP 65