- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Sleeve sensor with temperature measuring transducer
THERMASGARD® HFTM - Modbus - T3
Calibratable sleeve temperature measuring transducer THERMASGARD® HFTM - Modbus - T3,
with Modbus connection, in an impact-resistant plastic housing with quick-locking screws,
cable sensor with a stainless steel sleeve, optionally with/ without display, measures
temperature (–50...+150 °C). International system of units SI (default) can be changed
to imperial (via Modbus).
The sleeve sensor is used to detect the temperature in liquid and gaseous media. It is used as a duct sensor or, if installed in immersion sleeve THE (accessories), as an immersion and screw-in sensor in liquids.
The sleeve sensor is used to detect the temperature in liquid and gaseous media. It is used as a duct sensor or, if installed in immersion sleeve THE (accessories), as an immersion and screw-in sensor in liquids.
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable
bus termination resistance, DIP switch for setting the bus parameters and bus address in
current-free state, internal LEDs for telegram status display, two separate push-in terminals
and large three-line display (illuminated, with customised programming in the 7-segment range
and dot-matrix range). Uses internal diagnostics to detect sensor breakage or sensor short
circuit as errors. The error messages can be retrieved via Modbus and are shown on the display.
The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
(Perfect Sensor Protection)
Measuring range
-58...+302°F
Accuracy
typically ± 0.4 °F at +77 °F
Zero point offset
± 18 °F
Ambient temperature
Measuring transducer –22 … +158°F
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Sensor protection
stainless steel, 1.4571, V 4A, Ø = 0.24 in
HTF 50 NL = 2 in
(other optional dimensions also available, NL = 1.18...16 in)
cable entry stamped
HTF 50 NL = 2 in
(other optional dimensions also available, NL = 1.18...16 in)
cable entry stamped
Electrical connection
AWG 24 - 16, via push-in terminal
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 0,3 - 0,5 in) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 0,3 - 0,5 in) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Cable gland
2x M 20 x 1.5; with strain relief, replaceable,
inner diameter 0.3 - 0.5 in
inner diameter 0.3 - 0.5 in
sensor cable
Silicone, SiHF, 2 x 24 AWG; cable length (KL) = 5 ft
(other lengths and jacket materials, e.g. PTFE or
glass fibre with steel mesh, available on request)
(other lengths and jacket materials, e.g. PTFE or
glass fibre with steel mesh, available on request)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) sleeve humidity-tight (standard)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) housing / with glass fibre cable (optional)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) housing / with glass fibre cable (optional)
Units
switchable metric / imperial
Internal diagnostics
Error 1 at sensor breakage
Error 2 at sensor short circuit
Error 2 at sensor short circuit