temperature Pressure

Pressure, differential pressure and volume flow measuring transducers PREMASGARD® 212x

Product group: WG01

In Stock

Usually ships in 1 to 3 days
$ 470.01
$ 559,31 incl. sales tax + shipping
+

Description

Pressure, differential pressure and volume flow measuring transducers PREMASGARD® 212x
The calibratable compact pressure transmitters of the PREMASGARD® 212x series are equipped with 8 switchable measuring ranges, 2 switchable output signals (16 devices in one) and with/without optional display. They are used for measuring above-atmospheric, below-atmospheric or differential pressures and volume flow in air. The piezoresistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy.
These pressure measuring transducers have a pushbutton for manual zero-point calibration and an adjustable offset. Applications are found in cleanroom, medical and filter engineering, in ventilation and air conditioning ducts, in spray booths and large-scale catering facilities, in filter monitoring and level measuring or frequency converter triggering. Media measured with these pressure transducers are air (non-precipitating) or other gaseous, non-aggressive, non-combustible media. The differential pressure sensors are supplied including an ASD-06 connection set (2 m connection hose, two pressure connection nipples, screws).

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1 W at 24 V DC; < 2 VA at 24 V AC
Working resistance
Ra (Ohm) = 25 ...450 Ohm for I variant
Load resistance
RL > 25 kOhm for U variant
Output
switchable 0 -10 V/ 4...20 mA (via DIP switches)
Connection type
3-wire connection
Measuring function
Differential pressure, volume flow (square root output signal)
Current consumption
< 45 mA
Measuring ranges
multi-range switching with 8 switchable measuring ranges
Media temperature
–4...+122 °F (temperature-compensated +32...+122 °F)
Pressure connection
with connection nozzles for pressure hose Ø 0.24 in
Type of pressure
differential pressure
Zero point offset
± 5 % of final value
Medium
clean air and
non-aggressive, non-combustible gases
Signal filtering
switchable 1 s/ 10 s (via DIP switches)
Electrical connection
AWG 16 - 26 via terminal screws

Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 0.4 in
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 0.4 in) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Long-term stability
± 1 % per year
Hysteresis
0.3 % of final value
Media contacting parts
Brass, Ni, Duroplast, Si, epoxy, RTV, BSG, UV silicone gel
Linearity
< ± 1 % of final value
Air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 67 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No. 713139052 (Tyr 1)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU