temperature Temperature
temperature Luftfeuchtigkeit

HYGRASGARD® KFTF-Modbus-T3

Product group: WG01

In Stock

Usually ships in 1 to 3 days
$ 241,26
$ 234.99
$ 279,64 incl. sales tax + shipping
+

Description

HYGRASGARD® KFTF - Modbus - T3
Calibratable duct humidity and temperature sensor HYGRASGARD® KFTF - Modbus - T3 (± 2.0%) or KFTF - 20 - Modbus - T3 (± 1.8%), with Modbus connection, in an impact-resistant plastic housing with quick-locking screws, optionally with/ without display, with a plastic sinter filter (exchangeable), incl. mounting flange, to exactly detect the relative humidity (0…100% RH) and the temperature (–35...+80 °C) and to detect various parameters in humidity measurement. International system of units SI (default) can be switched to Imperial (via Modbus).

The duct sensor is applied in a non-aggressive, dust-free environment and is suitable for installation in ceilings, ducts and devices. It is used in the refrigeration, air conditioning and clean room technology, engineering rooms, hotels and conference facilities.

A long-term stable, digital humidity and temperature sensor guarantee exact measurement results. These measurands are used to internally calculate the following parameters that can be retrieved via Modbus: relative humidity, absolute humidity, mixture ratio, dew point, enthalpy (ignoring atmospheric air pressure) and ambient temperature.
Innovative Modbus sensor with galvanically separated RS485-Modbus-interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in curent-free state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Data points
Temperature [°F], relative humidity [% RH],
dew point [°F], absolute humidity [gr/ft³],
mixture ratio [gr/lb], enthalpy [Btu/lb]
Temperature deviation
typically ± 0.4 °F at +77 °F
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Sensor protection
plastic sinter filter, Ø 0.63 in, L = 1.38 in, exchangeable
(optional metal sinter filter, Ø 0.63 in, L = 1.26 in)
Measuring range
0...100 % RH (humidity)
-31...+176 °F (temperature)
Measuring ranges
0...100 % RH
-31...+176 °F
Zero point offset
± 10 % RH (humidity)
± 9 °F (temperature)
Ambient temperature
-22...+158 °F
Medium
clean air and
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
4 s / 32 s
Process connection
by mounting flange, plastic
(included in the scope of delivery)
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection,
Ø 0.79 in, NL = 9.3 in (optionally 3.9 in), vmax = 98.4 ft/s (air)
(option on request in stainless steel V2A (1.4301), Ø 0.63 in)
Electrical connection
AWG 24 - 16, via push-in terminal
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 0,3 - 0,5 in) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Long-term stability
± 1 % per year
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Protection type housing
IP 65