- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Duct humidity- and temperature sensors
HYGRASGARD® KFTF - Modbus RJ12
Calibratable HYGRASGARD® KFTF - Modbus - T3 (±2.0%) or KFTF - 20 - Modbus - T3 (±1.8%) duct humidity and temperature transmitters with Modbus connection, in an impact resistant plastic housing with quick-locking screws, optionally with/without display and including a mounting flange. They have a plastic sinter filter (exchangeable) and serve to detect various parametres in humidity measurement. measurands include relative humidity (0...100% RH) and ambient air temperature (– 31...+176 °F).
Innovative Modbus sensor with galvanically separated RS485 interface, selectable bus termination resistance, DIP switches for setting the bus parametres and bus address in current-free state, LEDs for telegram status display, two separate push-in terminals and a large back-lit three-line display with customised programming in the 7-segment and dot-matrix ranges. The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Data points
Temperature [°F], relative humidity [% RH],
dew point [°F], absolute humidity [gr/ft³],
mixture ratio [gr/lb], enthalpy [Btu/lb]
dew point [°F], absolute humidity [gr/ft³],
mixture ratio [gr/lb], enthalpy [Btu/lb]
Measuring range, humidity
0...100 % RH
Measuring range, temperature
-31...+176 °F
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
with integrated temperature sensor,
low hysteresis, high long-term stability
Sensor protection
plastic sinter filter, Ø 0.63 in, L = 1.38 in, exchangeable
(optional metal sinter filter, Ø 0.63 in, L = 1.26 in)
(optional metal sinter filter, Ø 0.63 in, L = 1.26 in)
Measuring ranges
0...100 % RH
-31...+176 °F
-31...+176 °F
Accuracy
typically ± 0.4 °F at +77 °F
Zero point offset
± 10 % RH (humidity)
± 9 °F (temperature)
± 9 °F (temperature)
Ambient temperature
-22...+158 °F
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
address range 0...247 selectable
Signal filtering
4 s / 32 s
Process connection
by mounting flange, plastic
(included in the scope of delivery)
(included in the scope of delivery)
Connection
RJ12 plug
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection,
Ø 0.79 in, NL = 9.3 in (optionally 3.9 in), vmax = 98.4 ft/s (air)
(option on request in stainless steel V2A (1.4301), Ø 0.63 in)
Ø 0.79 in, NL = 9.3 in (optionally 3.9 in), vmax = 98.4 ft/s (air)
(option on request in stainless steel V2A (1.4301), Ø 0.63 in)
Electrical connection
AWG 24 - 16, via push-in terminal
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 0,3 - 0,5 in) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 0,3 - 0,5 in) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Cable gland
2x M 20 x 1.5; with strain relief, replaceable,
inner diameter 0.3 - 0.5 in
inner diameter 0.3 - 0.5 in
Long-term stability
± 1 % per year
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Protection type housing
IP 65
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU