Description
Duct CO2 sensor
AERASGARD® KCO2-W
Patented quality product (patent no. DE 10 2014 010 719.1)
Maintenance-free AERASGARD® KCO2-SD duct air quality measuring transducer with active output, automatic calibration (fixed), in a compact plastic enclosure with quick-locking screws, for determining the CO2 content of the air (0…2000 ppm/0...5000 ppm). The transmitter converts the measured values into a standard signal of 0-10 V.
Maintenance-free AERASGARD® KCO2-W duct air quality measuring transducer with active/switching output, automatic calibration (can be deactivated), in a compact plastic enclosure with quick-locking screws, optionally with/without display, for determining the CO2 content of the air (0…2000 ppm/0...5000 ppm). The transmitter converts the measured values into a standard signal of 0-10 V or 4...20 mA (switchable).
The sensor device is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.
The CO2 content is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range is calibrated for standard applications such as the monitoring of residential and conference rooms.
Maintenance-free AERASGARD® KCO2-SD duct air quality measuring transducer with active output, automatic calibration (fixed), in a compact plastic enclosure with quick-locking screws, for determining the CO2 content of the air (0…2000 ppm/0...5000 ppm). The transmitter converts the measured values into a standard signal of 0-10 V.
Maintenance-free AERASGARD® KCO2-W duct air quality measuring transducer with active/switching output, automatic calibration (can be deactivated), in a compact plastic enclosure with quick-locking screws, optionally with/without display, for determining the CO2 content of the air (0…2000 ppm/0...5000 ppm). The transmitter converts the measured values into a standard signal of 0-10 V or 4...20 mA (switchable).
The sensor device is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.
The CO2 content is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range is calibrated for standard applications such as the monitoring of residential and conference rooms.
Technical details
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Data points
Carbon dioxide (CO2)
Measuring range, CO2
multi-range switching (selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
0...2000 ppm; 0...5000 ppm
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ K or ± 0.5 % of measured value/ K
(whichever is higher)
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Warm up time
approx. 1 hour
Response time
approx. 1 minute,
minimum flow rate 0.3 m / s (air)
minimum flow rate 0.3 m / s (air)
Measuring range
0...2000 ppm / 0...5000 ppm
Ambient temperature
14...+140 °F
Process connection
by mounting flange, plastic
(included in the scope of delivery)
(included in the scope of delivery)
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection,
Ø 0.79 in, NL = 8 in, vmax = 98 ft/s (air)
Ø 0.79 in, NL = 8 in, vmax = 98 ft/s (air)
Electrical connection
AWG 16 - 26 via terminal screws
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 0.4 in) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
M12 connector according to DIN EN 61076-2-101 (optional on request)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 0.4 in
max. inner diameter 0.4 in
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type housing
IP 65
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,