Air flow monitor RHEASGARD® KLGFT / KLGFVT

Product group: WG01

In Stock

Usually ships in 1 to 3 days
$ 345,22
$ 336.24
$ 400,13 incl. sales tax + shipping
+

Description

Air flow monitor RHEASREG® KLGF / KLSW

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Start bridging
60 s (can be activated via DIP switch)
Measuring range, temperature
32...+122 °F
Measuring accuracy
1.6 ft/s + 3 % measured value
Warm up time
< 2 min
Response time
< 5 s
Output
automatically 0 -10 V/ 4...20 mA (via Automatic Output Switching - the device recognizes the required output type and automatically switches to U or I output), Changeover contact (24 V)
Output signal
linearized
Sensor
Calorimetric, temperature compensated, sensor breakage protection, with manual zero-point calibration (via button)
Reproducibility
± 1.0 % final value
Current consumption
approx. 4 VA
Measuring range
0.3...65 ft/s
Media temperature
+32…+158 °F
Ambient temperature
storage –4...+ 122 °F
operation +32...+ 122 °F
Medium
pollutant-free, non-precipitating air
Process connection
by mounting flange
(included in the scope of delivery)
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection, Ø 0.79 in, NL = 8.7 in, vmax = 98 ft/s (air), stainless steel V2A (1.4301), Ø 0.63 in available upon request as an option
Inserted length
8.7 in
Electrical connection
AWG 24 - 16, via push-in terminal
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 0.4 in) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Screwed socket
-
Housing dimensions
4.96 x 3.54 x 1,97 in (Tyr 2)
Cable gland
M 16 x 1.5, including strain relief, exchangeable,
max. inner diameter 0.4 in
Dimensions
4.96 x 3.54 x 1,97 in (Tyr 2)
Long-term stability
± 0.5 % final value per year
Humidity
< 98% RH pollutant-free, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP65, Sensors IP 20
Protection type (sensor)
IP20
Protection type housing
IP 65 (according to EN 60 529)*
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
Display
Optional:
Display with illumination, three lines,
cut-out approx. 2.8 x 1.6 in (W x H),
for display of flow velocity (KLSW-W24, KLGF)
Reproducibility
± 1,0 % EW