Product description
- Measuring range: – 50...+ 150 °C / – 58...+ 302 °F
- Inserted Length: 100 mm
- Output: Modbus
- Protection type: IP 67
Patented quality product (Immersion sensor patent no. DE 10 2012 017 500.0)
Calibratable temperature measuring transducer with sensor tube THERMASGARD® TM65-Modbus-SD 100mm LCD, with Modbus connection (Y-adapter), in an impact-resistant plastic housing with quick-locking screws, stainless steel-protective tube (100 mm), with display, measures temperature (–50...+150 °C / – 58...+ 302 °F). International system of units SI (default) can be changed to imperial (via Modbus).
The duct sensor is used to detect the temperature in liquid or gaseous media. Use the stainless steel immersion sleeves for aggressive media. It is used in heating engineering, ventilation and air conditioning ducts, pipes, storage systems, compact district heating stations, warm and cold water systems, oil and lubrication cycle systems, machine and systems engineering and the entire industry sector.
Modbus sensor SD with RS485 Modbus interface (not galvanically isolated), selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display (illuminated, with customised programming). Uses internal diagnostics to detect sensor breakage or sensor short circuit as errors. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
Calibratable temperature measuring transducer with sensor tube THERMASGARD® TM65-Modbus-SD 100mm LCD, with Modbus connection (Y-adapter), in an impact-resistant plastic housing with quick-locking screws, stainless steel-protective tube (100 mm), with display, measures temperature (–50...+150 °C / – 58...+ 302 °F). International system of units SI (default) can be changed to imperial (via Modbus).
The duct sensor is used to detect the temperature in liquid or gaseous media. Use the stainless steel immersion sleeves for aggressive media. It is used in heating engineering, ventilation and air conditioning ducts, pipes, storage systems, compact district heating stations, warm and cold water systems, oil and lubrication cycle systems, machine and systems engineering and the entire industry sector.
Modbus sensor SD with RS485 Modbus interface (not galvanically isolated), selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display (illuminated, with customised programming). Uses internal diagnostics to detect sensor breakage or sensor short circuit as errors. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
Technical data
| Voltage supply | 24 V AC (± 20 %) and 15…36 V DC (± 10 %) |
| Power consumption | < 1.0 W/ 24 V DC < 2.2 VA/ 24 V AC |
| System of units | SI (default) or Imperial (switchable via Modbus) |
| Data points | Temperature [°C] [°F] |
| Sensor | Pt1000 DIN EN 60751 class B (Perfect Sensor Protection) |
| Measuring range | – 50...+ 150 °C / – 58...+ 302 °F |
| Accuracy temperature | typical ± 0.2 K at +25 °C |
| Zero point offset | ± 10 °K |
| Ambient temperature | Measuring transducer –30...+70 °C |
| Medium | Depending on selected immersion sleeve |
| Error detection | Sensor breakage sensor short circuit |
| Bus interface | RS 485 not galvanically isolated bus termination activatable via DIP switches. Up to 32 devices possible in one segment. In case of a greater number of devices RS485 repeaters must be used. |
| Bus protocol | Modbus (RTU mode) address range 0... 247 selectable |
| Baud rate | 9600 19200 38400 Baud |
| Status display | LED green = Telegram valid LED red = Telegram error |
| Signal filtering | 0.3 s / 1 s / 10 s |
| Protective tube | Stainless steel V4A (1.4571) Ø =6 mm inserted length (EL) = 100 mm (see table) |
| Housing | Plastic UV-resistant material polyamide 30 % glass-globe reinforced with quick-locking screws (slotted/ Phillips head combination) colour traffic white (similar to RAL 9016) housing cover for display is transparent! |
| Housing dimension | 72 x 64 x 43.3 mm (Tyr 1 with display) |
| Cable connection | Cable gland plastic 2x M 12 x 1.5 (Y-adapter) with strain relief exchangeable max. inner diameter 6 mm |
| electrical connection | 0.14 - 1.5 mm² via terminal screws |
| Permissible humidity | < 95 % RH non-precipitating air |
| Protection class | III (according to EN 60 730) |
| Protection type | IP 67 (according to EN 60 529)* housing tested TÜV SÜD Report No. 713139052 (Tyr 1) * Housing in the built-in state |
| Standards | CE conformity according to EMC Directive 2014/ 30/ EU |
| Optional | Display with illumination two-line programmable cutout approx. 36 x15 mm (W x H) for displaying the actual temperature error message or an individually programmable display value |