Product description
- Measuring range: – 50...+ 150 °C / – 58...+ 302 °F
- Output: Modbus
- Protection type: IP 65
Calibratable outside temperature measurement transducer ATM 2-Modbus-SD, with Modbus connection (Y-adapter), external sensor, housing made from impact-resistant plastic with quick-release screws, measures temperature (– 50...+ 150 °C / – 58...+ 302 °F).
The on-wall sensor is used to detect the temperature in gaseous media. It is used outside or in wet rooms, in cold storage buildings and greenhouses, in the industrial sector and in agriculture.
Installation on outside walls is preferably performed on the north side or in a protected place. In case of direct solar irradiation, we recommend the use of our sun and ball-impact protection hood WS 01 or WS 04 (accessories) or the device version with the installed sun protection SS 02 (on request).
Modbus sensor SD with RS485 Modbus interface (not galvanically isolated), selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display (illuminated, with customised programming).
Uses internal diagnostics to detect sensor breakage or sensor short circuit as errors.
The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
The on-wall sensor is used to detect the temperature in gaseous media. It is used outside or in wet rooms, in cold storage buildings and greenhouses, in the industrial sector and in agriculture.
Installation on outside walls is preferably performed on the north side or in a protected place. In case of direct solar irradiation, we recommend the use of our sun and ball-impact protection hood WS 01 or WS 04 (accessories) or the device version with the installed sun protection SS 02 (on request).
Modbus sensor SD with RS485 Modbus interface (not galvanically isolated), selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display (illuminated, with customised programming).
Uses internal diagnostics to detect sensor breakage or sensor short circuit as errors.
The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
Technical data
| Voltage supply | 24 V AC (± 20 %) and 15…36 V DC (± 10 %) |
| Power consumption | < 1.0 W/ 24 V DC < 2.2 VA/ 24 V AC |
| System of units | SI (default) or Imperial (switchable via Modbus) |
| Data points | Temperature [°C] [°F] |
| Sensor | Pt1000 DIN EN 60751 class B (Perfect Sensor Protection) |
| Measuring range | – 50...+ 150 °C / – 58...+ 302 °F |
| Accuracy temperature | typical ± 0.2 K at +25 °C |
| Zero point offset | ± 10 K |
| Ambient temperature | Measuring transducer –30...+70 °C |
| Medium | clean air and non-aggressive non-combustible gases |
| Error detection | Sensor breakage sensor short circuit |
| Bus interface | RS 485 not galvanically isolated bus termination activatable via DIP switches. Up to 32 devices possible in one segment. In case of a greater number of devices RS485 repeaters must be used. |
| Bus protocol | Modbus (RTU mode) address range 0...247 selectable |
| Baud rate | 9600 19200 38400 Baud |
| Status display | LED green = Telegram valid LED red = Telegram error |
| Signal filtering | 0.3 s / 1 s / 10 s |
| Protective tube | made from stainless steel V4A (1.4571) Ø 6 mm NL = 65 mm |
| Housing | Plastic UV-resistant material polyamide 30 % glass-globe reinforced with quick-locking screws (slotted/ Phillips head combination) colour traffic white (similar to RAL 9016) |
| Housing dimension | 72 x 64 x 37.8 mm (Tyr 1 without display) |
| Cable connection | Cable gland plastic 2x M 12 x 1.5 (Y-adapter) with strain relief exchangeable max. inner diameter 6 mm |
| Electrical connection | 0.14 - 1.5 mm² via terminal screws |
| Process connection | by screws |
| Permissible humidity | < 95 % RH non-precipitating air |
| Protection class | III (according to EN 60 730) |
| Protection type | IP 65 (according to EN 60 529) housing tested TÜV SÜD Report No.713139052 (Tyr 1) |
| Standards | CE conformity according to EMC Directive 2014/ 30/ EU |
We also manufacture individually
Do you have special requirements? As a manufacturer with our own production facilities in Germany, we are always in a position to produce products outside the standard range.
Contact us
Secure payment methods
Do you have a question? We are at your disposal:
+49 911 519 470
Mo. - Fr. 7.00am - 5.00pm CEST