Description
Pressure and differential pressure measuring transducers
PREMASGARD® 232x - Modbus - T3
W-Modbus is a wireless-based further development of the proven Modbus
standard for the wireless connection of Modbus-enabled sensors,
controllers and devices. W-Modbus devices communicate via a wireless
radio link from LumenRadio - independently of the in-house Wi-Fi and
without leaving the proven protocol standards. Thanks to the reliable
and interference-resistant wireless network, entire buildings can be
networked and the majority of Modbus RTU cables can be replaced.
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable bus termination
resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal
LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated;
with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated;
an environmental precision adjustment by an expert is possible.
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Data points
differential pressure
Media temperature
–20...+50 °C (temperature-compensated 0...+50 °C)
Pressure connection
with connection nozzles for pressure hose Ø 6 mm
Type of pressure
differential pressure
Zero point offset
± 5 % of final value
Above- below-pressure
máx. ± 50 kPa
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable gland
2x M 20 x 1.5; with strain relief, replaceable,
inner diameter 8 - 13mm
inner diameter 8 - 13mm
Pressure range
±7000Pa
Long-term stability
± 1 % per year
Communication
W-Modbus (Wireless Modbus with 2.4 GHz ISM)
Hysteresis
0.3 % of final value
Media contacting parts
Brass, Ni, Duroplast, Si, epoxy, RTV, BSG, UV silicone gel
Temperature drift values
± 0.1 %/ °C
Linearity
< ± 1 % of final value
Permissible air humidity
< 95 % RH, non-precipitating air
Accuracy
± 35 Pa
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Protection type housing
IP 65
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326, ETSI 300 328
according to EMC Directive 2014/ 30/ EU, Radio Directive 2014 / 53 / EU
electromagnetic compatibility according to EN 61326, ETSI 300 328
according to EMC Directive 2014/ 30/ EU, Radio Directive 2014 / 53 / EU
Optional
two-line display with illumination, programmable,
cutout approx. 36 x 15 mm (W x H), to display ACTUAL pressure
or an individually programmable display value (The Modbus interface allows the display to beindividually configured in the 7-segment area andin the dot-matrix area.)
cutout approx. 36 x 15 mm (W x H), to display ACTUAL pressure
or an individually programmable display value (The Modbus interface allows the display to beindividually configured in the 7-segment area andin the dot-matrix area.)