Description
Outside temperature/ wet room temperature measuring transducers
THERMASGARD® ATM 2 - VA
Calibratable THERMASGARD® ATM 2 - VA outside temperature measuring transducer with eight switchable measuring ranges, external sensor, continuous output, rugged housing in V4A stainless steel, with cable gland or M12 connector according to DIN EN 61076-2-101.
The transmitter serves to detect outside temperatures and temperatures in wet rooms. It is used e.g. on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas is preferably performed at the north side of a building or in a protected place. In cases of direct solar irradiation, we recommend using our WS 01 or WS 03 sun and ball-impact protection hood (accessory).
The transmitter serves to detect outside temperatures and temperatures in wet rooms. It is used e.g. on outside walls, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation in outdoor areas is preferably performed at the north side of a building or in a protected place. In cases of direct solar irradiation, we recommend using our WS 01 or WS 03 sun and ball-impact protection hood (accessory).
The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
Technical details
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
< 2,2 VA/ 24 V AC
Voltage supply
15...36 V DC
depending on working resistance, residual ripple stabilised ± 0.3 V
depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance
Ra (ohm) = (Ub -14 V)/ 0.02 A for I variant
Temperature deviation
typically ± 0.4 °F at +77 °F
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
(Perfect Sensor Protection)
Connection type
2-wire connection
Ambient temperature
Measuring transducer –22 … +158°F
Process connection
by screws
Protective tube
stainless steel V4A (1.4571), Ø 0.24 in, NL = 2.56 in
Electrical connection
AWG 16 - 26 via terminal screws
Housing dimensions
143 x 97 x 61 mm (Tyr 2E)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No.713139052 (Tyr 1)
TÜV SÜD, Report No.713139052 (Tyr 1)
Output
4...20 mA
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
see table (other ranges optional)
operating range –30...+70 °C
with manual zero point correction (± 10 K)
Cable connection
M12 connector
(male, 5-pin, A-code)
according to DIN EN 61076-2-101
(male, 5-pin, A-code)
according to DIN EN 61076-2-101
Housing
stainless steel V4A (1.4571),
with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, UV and weathering resistant
with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, UV and weathering resistant
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU