- New
- Sale
- Temperature
- Humidity
- Pressure
- Light Intensity & Motion
- Air Quality
- Flow
- Modbus | Wireless Modbus
- Room controller
- EtherCAT P
- Accessory
Description
Room humidity and temperature sensor
HYGRASGARD® RFTF - Modbus
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 1,2 W/ 24 V DC
< 2,2 VA/ 24 V AC
< 2,2 VA/ 24 V AC
Data points
Temperature [°F], relative humidity [% RH],
dew point [°F], absolute humidity [gr/ft³],
mixture ratio [gr/lb], enthalpy [Btu/lb]
dew point [°F], absolute humidity [gr/ft³],
mixture ratio [gr/lb], enthalpy [Btu/lb]
Measuring range, humidity
0...100 % RH
Deviation of humidity
typical ± 2.0 % (20…80 % RH); at + 25 °F, otherwise ± 3.0 %
Measuring range, temperature
32...+122 °F
Temperature deviation
typically ± 0.4 °F at +77 °F
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
with integrated temperature sensor,
low hysteresis, high long-term stability
Measuring range
0...100 % RH (humidity)
-31...+176 °F (temperature)
-31...+176 °F (temperature)
Zero point offset
± 10 % r.H. (humidity)
± 10 °C (temperature)
adjustable using potentiometer
± 10 °C (temperature)
adjustable using potentiometer
Ambient temperature
storage –31...+185 °F;
operation 32...+122 °F
operation 32...+122 °F
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Signal filtering
4 s / 32 s
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
colour pure white (similar to RAL 9010)
Dimensions
3.86 x 3.86 x 1.30 in (Baldur 2)
Installation
wall mounting or on in-wall flush box, Ø 2.2 in,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Long-term stability
± 1 % per year
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Standards
CE conformity
according to EMC Directive 2014/ 30/ EU,
according to EN 61 326
according to EMC Directive 2014/ 30/ EU,
according to EN 61 326
Units
switchable metric / imperial