Menu
Temperature
THERMASGARD® ALTM 2 - Modbus - T3

Surface contact temperature/ tube contact temperature measuring THERMASGARD® ALTM 2 - Modbus - T3

In Stock.

Usually ships in 1 to 3 days
133,63 €
Price plus Shipping
159,02 € Price plus shipping

Product group: WG01
Surface contact temperature/ tube contact temperature measuring THERMASGARD® ALTM 2 - Modbus - T3
Calibratable THERMASGARD® ALTM2-Modbus-T3 surface-contact temperature measuring transducer (detached version) with Modbus connection, in an impact resistant plastic housing with quick-locking screws, optionally with/without display, cable sensor with pipe feeder, and strap.

The pipe surface-contact sensor device serves to detect the temperature on lines and pipes (e.g. cold and warm water) or on heating sections for heating control.
Innovative Modbus transmitter with galvanically separated RS485 interface, selectable bus termination resistance, DIP switches for setting the bus parametres and bus address in current-free state, LEDs for telegram status display, two separate push-in terminals and a large back-lit three-line display with customised programming in the 7-segment range and dot-matrix ranges. Uses internal diagnostics to detect sensor breakage or shorts as errors. The error messages can be retrieved via Modbus and are shown on the display. The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection)
Measuring range
–50...+150 °C
Tmax up to +100 °C (compact variant)
Zero point offset
± 10 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Process connection
endless metal strap and metal tightener
(included in scope of delivery)
Strap dimensions
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable connection
cable gland, plastic
(2x M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Cable gland
2x M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm
sensor cable
silicone, SiHF, 2 x 0.25 mm², KL = 1.5 m (other lengths and jacket materials, e.g. PTFE or glass fibre with steel mesh, available on request)
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) humidity-tight stamped
IP 68 (optional watertight compound-filled) rolled
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Internal diagnostics
Error 1 at sensor breakage
Error 2 at sensor short circuit