Sleeve temperature measuring transducer HFTM-Modbus-SD
temperature Temperature

Sleeve temperature measuring transducer THERMASGARD® HFTM-Modbus-SD

Item no. 1101-6266-0210-120
EAN 4251325646206
Product group: WG01B

Low availability.

Usually ships in 3 to 5 days
132,56 €
106,05 € (special net price)
126,20 € incl. VAT + shipping
+

Description

Sleeve temperature measuring transducer THERMASGARD® HFTM - Modbus - SD
Calibratable sleeve temperature measuring transducer THERMASGARD® HFTM - Modbus-SD, with Modbus connection (Y-adapter), in an impact-resistant plastic housing with quick-locking screws, cable sensor with a stainless steel sleeve, ptionally with/ without display, measures temperature (–50...+150 °C).
The sleeve sensor is used to detect the temperature in liquid and gaseous media. It is used as a duct sensor or, if installed in immersion sleeve THE (accessories), as an immersion and screw-in sensor in liquids. Modbus sensor SD with RS485 Modbus interface (not galvanically isolated), selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display (illuminated, with customised programming). Uses internal diagnostics to detect sensor breakage or sensor short circuit as errors. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
Voltage supply
24 V AC (± 20 %) and
15…36 V DC (± 10 %)
Temperature deviation
typically ± 0.2 K at +25 °C
Measuring range
–50...+150 °C
Zero point offset
± 10 °C
Ambient temperature
Measuring transducer –30...+70 °C
Error detection
sensor breakage, sensor short circuit
Signal filtering
0,3 s / 1 s / 10 s
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Communication
RS485 interface, not galvanically isolated,
Bus termination activatable via DIP switches.
Sensor
Pt1000, DIN EN 60751, class B (Perfect Sensor Protection at IP68)
Medium
Clean air and non-aggressive, non-combustible gases;
liquids depending on selected immersion sleeve (accessory)
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Process connection
by screws
Insulating resistance
100 MΩ,
at +20 °C (500V DC)
Sensor protection
Sensor sleeve made from stainless steel V4A (1.4571), Ø = 6 mm,
nominal length (NL) = 50 mm (optional 30...400 mm)
Electrical connection
0.14 - 1.5 mm² via terminal screws
Cable connection
cable gland, plastic 2x M 12 x 1.5 (Y-adapter);
with strain relief, exchangeable,
max. inner diameter 6 mm
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
72 x 64 x 37.8 mm (Tyr 1 without display)
sensor cable
Silicone, SiHF, 2 x 0,25 mm²; cable length (KL) = 1.5 m
(other lengths and jacket materials, e.g. PTFE or
glass fibre with steel mesh, available on request)
Protection type (sensor)
IP 65 (according to EN 60 529) sleeve humidity-tight (standard)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
IP 54 (according to EN 60 529) with glass fibre cable (optional)
Protection type housing
IP 65 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No.713139052 (Tyr 1)
Standards
CE conformity, electromagnetic compatibility according to
EMC directive 2014/ 30/ EU, EN 61326
Optional
display with illumination, two-line,
programmable, cutout approx. 36 x15 mm (W x H),
for displaying the actual temperature, error message or
an individually programmable display value
Features
Baud rate: 9600, 19200, 38400 baud

Accessories