Sleeve temperature measuring transducer HFTM-Modbus LCD
temperature Temperature

Sleeve temperature measuring transducer THERMASGARD® HFTM-Modbus LCD

Item no. 1101-1256-2210-000
EAN 4251325600857
Product group: WG01

Currently not available

185,02 €
220,17 € incl. VAT + shipping
+

Description

Sleeve temperature measuring transducer THERMASGARD® HFTM - Modbus - SD
Calibratable THERMASGARD® HFTM - Modbus temperature measuring transducer with sleeve sensor, Modbus connection, terminal box housing made of impact resistant plastic, housing cover with quick-locking screws, with/without optional display for indicating the actual temperature.
The temperature transmitter with remote sensor serves to detect temperatures in liquid and gaseous media e.g. if installed in a thermowell or as a duct sensor. The device is factory-calibrated. Adjustment/Fine-tuning by the user is possible (zero-point offset is adjustable).

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B
Measuring range
–50...+150 °C
Zero point offset
± 10 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Sensor protection
stainless steel, 1.4571, V4A, Ø = 6 mm,
nominal length (NL) = 50 mm
(other dimensions optional)
cable entry stamped (optional rolled)
Connection cable
silicone, SiHF, 2 x 0.25 mm², KL = 1.5 m
(other lengths and jacket materials, e.g. PTFE or glass fibre with steel mesh, available on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016),
housing cover for display is transparent !
Housing dimensions
72 x 64 x 43.3 mm (Tyr 1 with Display)
Cable gland
2x M 12 x 1.5 (Y-adapter); with strain relief,
exchangeable, max. inner diameter 6 mm
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) humidity-tight stamped
IP 68 (optional watertight compound-filled) rolled
IP 54 (optional glass fibre cable)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Display
two-line display with illumination, programmable,
cutout approx. 36 x 15 mm (W x H),
for displaying the actual temperature or
an individually programmable display value
(The Modbus interface allows the display to be individually
configured in the 7-segment area and in the dot-matrix area.)

Accessories