Screw-in humidity and temperature sensor for pressure systems ESFTF
temperature Luftfeuchtigkeit
temperature Temperature

Screw-in humidity and temperature sensor for pressure systems HYGRASGARD® ESFTF

Product group: WG02

Low availability.

Usually ships in 3 to 5 days
544,81 €
648,32 € incl. VAT + shipping
+

Description

Screw-in humidity and temperature sensor for pressure systems HYGRASGARD® ESFTF
The humidity transmitters of the HYGRASGARD® ESFF / ESFTF series are used for measuring relative humidity and air temperature pressurised systems, and convert these measured values to standard signals of 4...20 mA or 0-10 V. Process connection is G ½" straight external pipe thread, with a terminal box housing made of impact resistant plastic, and housing cover with quick-locking screws.
The screw-in humidity measuring transducers have been designed for operation in pollutant-free, non-precipitating air. They are mounted vertically with the sensor pointing down.

Technical details

Voltage supply
24 V AC/DC (± 10 %) for U -variant;
15...36 V DC for I -variant, load-dependent
Power consumption
1.1 VA for U variant;1.5 W for I variant
Data points
Temperature [°C], relative humidity [% RH],
dew point [°C], absolute humidity [g / m3],
mixture ratio [g / kg]
Working resistance
RLmax = (UB - 15 V) / 0.02 A for I -variant, see load diagram
Measuring range, humidity
0...100 % RH
Deviation of humidity
typically ± 3.0 % (30...70 % RH) at +25 °C, otherwise ± 3.5 %
(deviation of the alternative parameters result
from the deviations of humidity and temperature).
Measuring range, temperature
multi-range switching with 4 switchable measuring ranges
0...+50 °C (default); –20...+80 °C; –30...+70 °C; 0...+100 °C
Temperature deviation
typically ± 0.5 K at +25 °C
Nominalpressure
10 bar
Warm up time
< 5 min
Response time
< 60 s
Output
0 - 10 V for U variant; 4...20 mA for I variant
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Sensor protection
Metal sintered filter, Ø 20 mm, replaceable, with condensation protection due to heating function
Measuring ranges
0...100 % RH
0...+50 / –20...+80 / –30...+70 / 0...+100 °C
Ambient temperature
storage –20...+ 50 °C
operation 0...+ 50 °C
Process connection
screwed socket with G ½ " straight pipe thread, immersion depth 25 mm
Protective tube
made of metal, Ø 20 mm, NL = 115 mm, pressure resistance pmax = 10 bar
Electrical connection
3- or 4-wire connection
0.14 - 1.5 mm² via plug terminals
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced
colour traffic white (similar to RAL 9016)
ALTF 02 with snap-on lid,
Dimensions
72 x 64 x 37,8 mm (Tyr 1)
Installation
vertical mounting, humidity sensor at the bottom
Long-term stability
± 1 % per year
Humidity
< 99% RH, pollutant-free, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) in the built-in state,
Housing tested, TÜV SÜD, Report No. 713139052 (Tyr 1)
Protection type housing
IP 65
Function
Sensorschutzfunktion bei Hochfeuchte (95...99 % RH)
Übersteigt die relative Feuchte den werksseitig vorgegebenen Schwellwert von 95 % RH, wird eine zeitlich begrenzte Heizfunktion aktiviert und der Sensor vor Kondensation geschützt. In this operating state, the output signals remain at the last measured values before the heating function was activated.