RPS-SD - S+S Regeltechnik | Order online!
temperature Fine dust particulate

Room fine dust sensor/ particulate matter sensor incl. humidity, temperature, fine dust (PM) and CO2 AERASGARD® RPS-SD

Item no. 1501-2110-1001-000
EAN 4251325618906
Product group: WG02

In Stock

Usually ships in 1 to 3 days
316,30 €
376,40 € incl. VAT + shipping
+

Description

Room fine dust sensor/ particulate matter sensor incl. humidity, temperature, fine dust (PM) and CO2 AERASGARD® RPS-SD
Maintenance-free room sensor AERASGARD® RPS - SD with active output, in an elegant plastic housing
with snap-on lid, base with 4-hole attachment, for detecting the fine dust content (0...500 g/m3).
The measuring transducer converts the measurand into a standard signal of 0 -10 V (fixed).
Maintenance-free, multifunctional room sensor AERASGARD® RFTM - PS - CO2 - W with active/switching output,
automatic calibration, in an elegant plastic housing with snap-on lid, base with 4-hole attachment, optionally with/
without display, for detection of measurands air humidity (0...100 % r.H.), temperature (0...+50°C), fine dust (PM)
(0...50 / 100 / 300 / 500 g/m3) and CO2 content (0...2000 / 5000 ppm). The measuring transducer converts the
measurand into a standard signal of 0 -10 V or 4...20 mA (switchable).
Use just one device to monitor and control the entire indoor climate effectively. This enables energy-saving room
ventilation on an as-needed basis, thereby reducing operating costs and improving well-being. It is used in offices,
hotels, convention centres, apartments, shops, etc.
A long-term stable, digital humidity and temperature sensor guarantees exact measurement results.
The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology).
An optical particulate sensor precisely detects fine dust (PM) of the size category 0.3 to 10 micrometers.
The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.
Maintenance-free room sensor AERASGARD® RPS - SD with active output, in an elegant plastic housing
with snap-on lid, base with 4-hole attachment, for detecting the fine dust content (0...500 g/m3).
The measuring transducer converts the measurand into a standard signal of 0 -10 V (fixed).
Maintenance-free, multifunctional room sensor AERASGARD® RFTM - PS - CO2 - W with active/switching output,
automatic calibration, in an elegant plastic housing with snap-on lid, base with 4-hole attachment, optionally with/
without display, for detection of measurands air humidity (0...100 % r.H.), temperature (0...+50°C), fine dust (PM)
(0...50 / 100 / 300 / 500 g/m3) and CO2 content (0...2000 / 5000 ppm). The measuring transducer converts the
measurand into a standard signal of 0 -10 V or 4...20 mA (switchable).
Use just one device to monitor and control the entire indoor climate effectively. This enables energy-saving room
ventilation on an as-needed basis, thereby reducing operating costs and improving well-being. It is used in offices,
hotels, convention centres, apartments, shops, etc.
A long-term stable, digital humidity and temperature sensor guarantees exact measurement results.
The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology).
An optical particulate sensor precisely detects fine dust (PM) of the size category 0.3 to 10 micrometers.
The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Long-term stability (PM)
± 1.25 μg/m3 (± 1.25 % of measured value/year)
Measuring accuracy (PM)
typically ± 10 g/m3 (± 10 % of measured value) at PM 2.5
typically ± 25 g/m3 (± 25 % of measured value) at PM 10
Measuring range (PM)
0...50 / 0...100 / 0...300 / 0...500 μg/m³
Particle size (PM)
PM 2,5 (0,3...2,5 μm); PM 10 (0,3...10 μm)
Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
RPS-SD: < 1.5 W/ 24 V DC typical;
< 2.9 VA/ 24 V AC typical;
peak current 200 mA
Data points
Particulate matter (PM)
Service life
> 60 months (under normal load conditions)
depending on the type of loading and gas concentration
Warm up time
approx. 1 hour
Response time
< 2 minutes
Output
0 -10 V (fixed)
Measuring range
0...50 / 0...100 / 0...300 / 0...500 μg/m³
Ambient temperature
0...+50 °C
Electrical connection
0.14 - 1.5 mm² via terminal screws
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions
98 x 98 x 33 mm (Baldur 2)
Installation
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Protection type housing
IP 30
Standards
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014/ 30/ EU,
Low Voltage Directive 2014/ 35/ EU