Roomo-thermostat RHT - 30
temperature Luftfeuchtigkeit

Room hygro-thermostat HYGRASREG® RHT - 30

Product group: WG02

In Stock

Usually ships in 1 to 3 days
187,51 €
223,14 € incl. VAT + shipping
+

Description

Room hygro-thermostat HYGRASREG® RHT - 30
Electronic HYGRASREG® RHT-30 room hygrostat and/or room thermostat with one continuous and two switching outputs, adjustable switching thresholds, with/without optional display for indicating ACTUAL humidity and/or ACTUAL temperature (accuracy class ±2.0% r.H.). The setpoints can be allocated to relative humidity and/or temperature.
The sensor device is suitable for regulating and monitoring relative humidity (humidifying and dehumidifying) and/or temperature (heating and cooling) e.g. in ventilation and air conditioning ducts, laboratories, production facilities, climate test chambers, indoor swimming pools, greenhouses, etc., for humidifying and dehumidifying equipment or heating system control. The measuring transducer has been designed for exact humidity/temperature measurement. The RHT-30 uses a digital, long-term stable sensor as a measuring element. It is used in dust-free, unpolluted, non-aggressive air.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1.5 VA/ 24 V DC, < 3.5 VA/ 24 V AC
Load resistance
RL > 5 kOhm
Deviation of humidity
typical ± 2.0 % (20…80 % RH); at + 25 °C, otherwise ± 3.0 %

Temperature deviation
typically ± 0.2 K at +25 °C
Output
potential-free changeover contacts
(2 x changeover contact 24 V, 1A ohmic load, separately adjustable,
1x 0 - 10 V)
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Operating difference
Mode 1: both switch steps are freely adjustable (rel. humidity)
Mode 2: 5 % between both switch steps (rel. humidity)
Mode 3: both switch steps freely adjustable (temperature)
Mode 4: switch step 1 (temperature), switch step 2 (rel. humidity)
(adjustable via DiP switches)
Setting range
5...95 % r.H. (Humidity)
+5...+ 45 °C (Temperature)
(switch steps 1 and 2 are separately adjustable)
Ambient temperature
storage –35...+85 °C,
operation – 30...+70 °C, non-precipitating
Electrical connection
0.14 - 1.5 mm² via terminal screws
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Housing dimensions
98 x 98 x 35 mm (Baldur 2)
Installation
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Long-term stability
± 1 % per year
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Standards
CE conformity, EMC directive 2014/ 30/ EU
Function
Humidifying/heating:

1st step: wire contacts 11 - 12.
If actual humidity falls more than 3 % r.H. / 1 K (hysteresis) below
switching threshold S1, the changeover contact switches to 11 - 12.

2. step: wire contacts 21 - 22.
If actual humidity falls more than 3 % r.H. / 1 K (hysteresis) below
switching threshold S2, the changeover contact switches to 21 - 22.
Terminal 2: output relative humidity / temperature

Dehumidifying/cooling:

1st step: wire contacts 11 - 13.
When actual humidity exceeds switching threshold S1,
the changeover contact switches to 11 - 13.

2. step: wire contacts 21 - 23.
When actual humidity exceeds switching threshold S 2,
the changeover contact switches to 21 - 23.
Terminal 2: output relative humidity / temperature