Duct/ smoke gas temperature measuring transducer THERMASGARD® RGTM 1
Calibratable flue gas measuring transducer THERMASGARD® RGTM 1 with eight switchable measuring ranges, exchangeable spring-mounted measuring insert and straight protective tube, connecting head made of aluminium, metal mounting flange and continuous output for the detection of high temperatures in gaseous media, e.g. for exhaust air or flue gas temperature measurement. These sensors are factory-calibrated. Adjustment/ fine adjustment by the user is possible (range and zero point are adjustable).
Calibratable flue gas measuring transducer THERMASGARD® RGTM 1 with eight switchable measuring ranges, exchangeable spring-mounted measuring insert and straight protective tube, connecting head made of aluminium, metal mounting flange and continuous output for the detection of high temperatures in gaseous media, e.g. for exhaust air or flue gas temperature measurement. These sensors are factory-calibrated. Adjustment/ fine adjustment by the user is possible (range and zero point are adjustable).
Technical details
Power consumption
< 1.0 VA/ 24 V AC/ DC; < 0.55 VA/ 24 V DC
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor
Pt1000, DIN EN 60751, class B,
glass sensing resistor
(Perfect Sensor Protection)
Connection type
2- or 3-wire connection
Ambient temperature
Measuring transducer –30...+70 °C
Process connection
by mounting flange, stainless steel V2A (1.4305)
(included in the scope of delivery)
Protective tube
stainless steel, 1.4571, V4A, Ø = 8 mm
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Connecting head
form B, material aluminium,
colour white aluminium (similar to RAL 9006),
M 20 x 1.5
zulässige Luftfeuchte
< 95 % r. H., non-precipitating air
Protection class
III (according to EN 60 730)
Measuring ranges
multi-range switching with 8 switchable measuring ranges,
see table (other ranges optional)
with manual zero point correction (± 10 K)
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,