room sensor for humidity, temperature, fine dust (PM) and CO2 RFTM-PS-W
temperature Temperature
temperature Luftfeuchtigkeit
temperature Fine dust particulate
temperature CO2

room sensor for humidity, temperature, fine dust (PM) and CO2 AERASGARD® RFTM-PS-W

Item no. 1501-2116-7301-000
EAN 4251325618852
Product group: WG02

In Stock

Usually ships in 1 to 3 days
412,61 €
491,01 € incl. VAT + shipping
+

Description

room sensor for humidity, temperature, fine dust (PM) and CO2 AERASGARD® RFTM-PS-CO2-W
Maintenance-free, multifunctional AERASGARD® RFTM - PS - CO2 - W room air quality measuring transducer with active/switching output, automatic calibration, in an elegant plastic housing with snap-on cover, base with 4-hole attachment, optionally with/without display, for detecting air humidity (0...100% RH), temperature (0...+50°C), particulate matter (PM) (0...50/100/300/500 μg/m3) and CO2 content (0...2000 / 5000 ppm). The transmitter converts the measured values into a standard signal of 0-10 V or 4...20 mA (switchable).

The multifunctional sensor device is ideal for effectively monitoring and controlling the entire indoor climate with just one device. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being. It is used in offices, hotels, convention centres, apartments, shops, etc.
A long-term stable, digital humidity and temperature sensor guarantees precise measuring results. The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). An optical particulate sensor precisely detects particulate matter (PM) of size categories 0.3 to 10 micrometres. The sensor is factory-calibrated and can be fine-tuned to ambient conditions by an expert.

Technical details

Long-term stability (PM)
± 1.25 μg/m3 (± 1.25 % of measured value/year)
Measuring range (PM)
0... 50 μg/m³ 0...100 μg/m³ 0...300 μg/m³ 0...500 μg/m³
Particle size (PM)
PM 2,5 (0,3...2,5 μm); PM 10 (0,3...10 μm)
Voltage supply
24 V AC/ DC (± 10 %)
Measuring accuracy (PM)
typically ± 10 g/m3 (± 10 % of measured value) at PM 2.5
typically ± 25 g/m3 (± 25 % of measured value) at PM 10
Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % RH (without dew formation)
Deviation of humidity
typical ± 2 % RH (20…80 % RH ); at + 25 °C, otherwise ± 3 %
Measuring range, temperature
0...+ 50 °C (output equivalent to 0 -10 V or 4...20 mA)
Power consumption
RFTM-PS-CO2-W: < 4.4 W/ 24 V DC typical; < 6.4 VA/ 24 V AC typical;
peak current 200 mA

Operating range, temperature
0...+50 °C
Data points
temperature, relative humidity, fine dust (PM)
Temperature deviation
typically ± 0.2 K at +25 °C
Output, humidity
0 -10 V or 4...20 mA (selectable via DIP switches)
Output, temperature
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring range
0...50 / 0...100 / 0...300 / 0...500 μg/m³
Ambient temperature
0...+50 °C
Electrical connection
0.14 - 1.5 mm² via terminal screws
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions
98 x 98 x 33 mm (Baldur 2)
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Protection type housing
IP 30
Service life
> 60 months (under normal load conditions)
depending on the type of loading and gas concentration
Measuring range, CO2
0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
Sensor, CO2
Optical NDIR sensor (non-dispersive infra-red technology),

with manual calibration (via zero button),
with automatic calibration (can be deactivated via DIP switches)
Output, CO2
0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Relay output
with potential-free changeover contact (24 V / 1 A)
(assignment selectable via DIP switches, switchpoint adjustable)
Warm up time
approx. 1 hour
Response time
< 2 minutes
Output
0 -10 V or 4...20 mA (selectable via DIP switches,
selected variant applies for all outputs), working resistance < 800 Ω
Output
0 -10 V or 4...20 mA, working resistance < 800 Ω
(selectable via DIP switches, selected variant applies for all outputs),
with offset potentiometer (± 10 % of the measuring range)
Measuring ranges
0...50 / 0...100 / 0...300 / 0...500 μg/m³
Installation
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Long-term stability
< 2 % in 15 years
Standards
CE conformity, electromagnetic compatibility
according to EN 61 326, EMC Directive 2014/ 30/ EU,
Low Voltage Directive 2014/ 35/ EU