Room motion sensor / presence detector and light sensor RBWF-LF-U
temperature Präsenz
temperature Light Intensity

Room motion sensor / presence detector and light sensor KINASGARD® RBWF-LF-U

Item no. 1401-41A1-1100-000
EAN 4251325612911
Product group: WG01

In Stock

Usually ships in 1 to 3 days
169,98 €
202,28 € incl. VAT + shipping
+

Description

Room motion sensor / presence detector and light sensor KINASGARD® RBWF/LF
The KINASGARD® / PHOTASGARD® RBWF / LF motion and light sensors are combined instruments and detect motion as well as the light intensity by means of a diffusor. They also detect the presence of persons and ambient conditions. The RBWF / LF devices issue a standard signal of 0-10 V or 4...20 mA for light intensity, and hav a switching (changeover contact) output for motion detection.
The multi-sensor devices are used in facility automation, in corridors, at workplaces, in industrial halls, offices and business facilities for on-demand lighting, sunshade and daylight-dependent constant lighting control, for activation of Venetian blinds or luminaires, for automatic energy conservation, and to avoid unnecessary heating or cooling of unoccupied rooms.

Technical details

Power consumption
< 1 W at 24 V DC; < 2 VA at 24 V AC
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Load resistance
RL > 5 kOhm
Output, motion sensor
without/ with motion + presence,
potential-free changeover contact (24 V), 1 A ohmic load
Sensor
infra-red motion sensor, light sensor with diffuser
After-running time
adjustable from 4 s to 16 min
Deviation, light sensor
typically < 5 % of final value
Ambient temperature
0...+50 °C
Electrical connection
0.14 - 1.5 mm²
via terminal screws on circuit board
Housing
plastic, material ABS,
colour pure white (similar to RAL 9010)
Dimensions
85 x 85 x 27 mm (Baldur 1)
Output, light sensor
0 -10 V (linearised, active, 3-wire connection)
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Measuring range, light sensor
multi-range switching (via DIP switches)
with 4 switchable measuring ranges
0...500 Lux/ 1 kLux/ 5 kLux/ 20 kLux
(other individual ranges optional, e. g. 100 kLux)
Installation
wall mounting or on in-wall flush box, Ø 55 mm,
base with 4 holes, for attachment to vertically or
horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry
from top/ bottom in case of plain on-wall installation
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU