Pressure and differential pressure measuring transducer / switch
PREMASREG® 114x
Quality product for the HVAC sector, accuracy ±1.5%
The electronic PREMASREG® 1141 pressure sensor device and switch supports eight switchable measuring ranges (eight devices in one) and features one switching output, one continuous output and a display for setting the switchpoint and showing the actual pressure. It serves as a differential pressure switch/monitor and continuous pressure sensor transmitter in a single unit.
The electronic PREMASREG® 1141 pressure sensor device and switch supports eight switchable measuring ranges (eight devices in one) and features one switching output, one continuous output and a display for setting the switchpoint and showing the actual pressure. It serves as a differential pressure switch/monitor and continuous pressure sensor transmitter in a single unit.
The pressure sensor device is used for above-atmospheric, below-atmospheric or differential pressure measurement in clean air, including limit value switching. The piezoresistive measuring element guarantees a high level of reliability and accuracy. Applications are found in cleanroom, medical and filter engineering, in ventilation and air conditioning ducts, in spray booths and large-scale catering facilities, in filters monitoring and level measurement or frequency converter triggering. Media measured by the pressure measuring transducer are air (non-precipitating) or gaseous, non-aggressive, non-combustible media. The pressure sensor device has a manual zero-point pushbutton and an offset potentiometer for correction of the final value and the switching point. Fine adjustment by the user is possible at any time. Our ASD-06 connection set (2 m connection hose, two pressure connection nipples, screws) is included in the scope of supply.
Technical details
Voltage supply
24 V AC/ DC (± 20 %)
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
< 2,2 VA/ 24 V AC
Load resistance
RL > 5 kOhm
Pressure range
±1000Pa
Output signal
0 -10 V
1 changeover contact (24 V), 1 A ohmic load
1 changeover contact (24 V), 1 A ohmic load
Measuring ranges
multi-range switching with 8 switchable measuring ranges
Media temperature
–20...+50 °C
Pressure connection
with metal connection nozzles for pressure hose Ø 6 mm
Type of pressure
differential pressure
Accuracy
(1000 Pa): typically ± 5 Pa
compared to the calibrated reference device
compared to the calibrated reference device
Accuracy, pressure
± 5 Pa
Zero point offset
< ± 0.7 % of final value
Above- below-pressure
máx. ± 200 hPa
Measuring range pressure
0 ... +100 Pa / -100 ... +100 Pa
0 ... +300 Pa / -300 ... +300 Pa
0 ... +500 Pa / -500 ... +500 Pa
0 ... +1000 Pa / -1000 ... +1000 Pa
0 ... +300 Pa / -300 ... +300 Pa
0 ... +500 Pa / -500 ... +500 Pa
0 ... +1000 Pa / -1000 ... +1000 Pa
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Signal filtering
switchable 1 s/ 10 s
Setting increment p
1 % of pressure range (100 Pa => 1 Pa; 5000 Pa => 50 Pa)
Switching hysteresis
± 1 % of pressure range (100 Pa => ± 1 Pa; 5000 Pa => ± 50 Pa)
Electrical connection
3-wire connection (U)
0.14 - 1.5 mm², via removable plug-in screw terminals
0.14 - 1.5 mm², via removable plug-in screw terminals
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
Cable gland
M 16 x 1.5; including strain relief
Dimensions
108 x 72.5 x 70 mm (Thor 2)
Sum of Linearity+hysteresis
< ± 1 % of final value
Temperature drift values
± 0.1 %/ °C
Air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
Features
two-line display with illumination, cutout approx. 36 x 15 mm (W x H),
for displaying ACTUAL pressure and/ or SETPOINT pressure
or undercutting or exceeding the measuring range
for displaying ACTUAL pressure and/ or SETPOINT pressure
or undercutting or exceeding the measuring range