Volume flow meter
PREMASREG® 116x
The calibratable PREMASGARD® 1161 and PREMASREG® 1160 pressure transmitters are used for measuring above-atmospheric, below-atmospheric, or differential pressures in air for volume flow rate indication. The piezoresistive measuring element guarantees a high degree of reliability and accuracy.
These pressure sensor devices are used in cleanroom, medical and filter engineering, in ventilation and air conditioning ducts, in spray booths and large-scale catering facilities, in filter monitoring, level measuring or frequency verter triggering. measured media are (non-precipitating) or gaseous, non-aggressive, non-combustible media.
Technical details
Measuring range Volume flow
212100 m³/h
Voltage supply
24 V AC/ DC (± 20 %)
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
< 2,2 VA/ 24 V AC
Load resistance
RL > 5 kOhm
Pressure range
5000 Pa
Output signal
0 - 10 V
Measuring ranges
1000 Pa/ 5000 Pa
Media temperature
–20...+50 °C
Pressure connection
4/ 6 x 11 mm (hoses Ø = 4/ 6 mm),
metal pressure connection nozzles
metal pressure connection nozzles
Type of pressure
differential pressure
Accuracy
(5000 Pa): typically ± 25 Pa
compared to the calibrated reference device
compared to the calibrated reference device
Accuracy, pressure
± 25 Pa
Zero point offset
< ± 0.7 % of final value
Above- below-pressure
máx. ± 200 hPa
Measuring range pressure
0 ... 5000 Pa
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Signal filtering
switchable 1 s/ 10 s
Electrical connection
3-wire connection
0.14 - 1.5 mm², via removable plug-in screw terminals
0.14 - 1.5 mm², via removable plug-in screw terminals
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
material polyamide, 30 % glass-globe-reinforced,
colour traffic white (similar to RAL 9016)
Cable gland
M 16 x 1.5; including strain relief
Dimensions
108 x 72.5 x 70 mm (Thor 2)
Sum of Linearity+hysteresis
< ± 1 % of final value
Temperature drift values
± 0.1 % of pressure range end value per °C
Air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Standards
CE conformity,
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
according to EMC directive 2014/ 30/ EU,
according to EN 61326-1, according to EN 61326-2-3
Features
two-line display with illumination,
cutout approx. 36 x15 mm (W x H),
displaying the volume flow rate
cutout approx. 36 x15 mm (W x H),
displaying the volume flow rate
K factor
1 to 3000
Units
adjustable
m³/ s, m³/ min, m³/ h, litres/ s, lighters/ min, lighters/ h
m³/ s, m³/ min, m³/ h, litres/ s, lighters/ min, lighters/ h
Max. value displayed
999999