Description
Outside temperature/ wet room temperature measuring transducers
THERMASGARD® ATM 2 - Modbus - T3
Calibratable outside temperature measurement transducer THERMASGARD®
ATM 2 - Modbus - T3, with Modbus connection, in an impact-resistant plastic housing with
quick-locking screws, optionally with/ without display, measures temperature (–50...+150 °C).
International system of units SI (default) can be changed to imperial (via Modbus).
The on-wall sensor is used to detect the temperature in gaseous media. It is used outside or in wet rooms, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation on outside walls is preferably performed on the north side or in a protected place. In case of direct solar irradiation, we recommend using our sun and ball-impact protection hood WS 01 or WS 04 (accessories).
The on-wall sensor is used to detect the temperature in gaseous media. It is used outside or in wet rooms, in cold storage buildings and greenhouses, in the industrial sector and in agriculture. Installation on outside walls is preferably performed on the north side or in a protected place. In case of direct solar irradiation, we recommend using our sun and ball-impact protection hood WS 01 or WS 04 (accessories).
Innovative Modbus sensor with galvanically separated RS485 Modbus interface, selectable
bus termination resistance, DIP switch for setting the bus parameters and bus address in
current-free state, internal LEDs for telegram status display, two separate push-in terminals
and large three-line display (illuminated, with customised programming in the 7-segment
range and dot-matrix range). Uses internal diagnostics to detect sensor breakage or sensor
short circuit as errors. The error messages can be retrieved via Modbus and are shown on
the display. The sensor is factory-calibrated; an environmental precision adjustment by an
expert is possible.
Technical details
Voltage supply
24 V AC (± 20 %) and
15…36 V DC
15…36 V DC
Power consumption
< 1.2 W/ 24 V DC; < 1.8 VA/ 24 V AC
Data points
température [°C] [°F]
Sensor
Pt1000, DIN EN 60751, class B
Measuring range
–50...+150 °C
Accuracy
typically ± 0.2 K at +25 °C
Zero point offset
± 10 °C
Ambient temperature
Measuring transducer –30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
non-aggressive, non-combustible gases
Error detection
sensor breakage, sensor short circuit
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
address range 0...247 selectable
Signal filtering
0,3 s / 1 s / 10 s
Process connection
by screws
Electrical connection
0.2 - 1.5 mm², via push-in terminal
Cable connection
cable gland, plastic
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 8 - 13 mm) or
M12 connector according to DIN EN 61076-2-101
(optional on request)
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Units
switchable metric / imperial
Internal diagnostics
Error 1 at sensor breakage
Error 2 at sensor short circuit
Error 2 at sensor short circuit