Multifunctional on-wall sensors and measuring transducers, for humidity, temperature, CO2 content and air quality (VOC) AERASGARD® AFTM-LQ-CO2-Modbus

Item no. 1501-7118-6001-500
EAN 4251325624112
Product group: WG02

In Stock

Usually ships in 1 to 3 days
619,86 €
737,63 € incl. VAT + shipping
+

Description

Multifunctional on-wall sensors and measuring transducers, for humidity, temperature, CO2 content and air quality (VOC) AERASGARD® AFTM-LQ-CO2 - Modbus
The maintenance-free on-wall sensor AERASGARD® AFTM - LQ- CO2 - Modbus (max. expansion level) and AFTM - CO2 - Modbus with Modbus connection, automatic calibration, in an impact- resistant plastic housing with quick-locking screws, plastic sinter filter (replaceable), optionally with/without display, for determining the CO2-content of the air (0...5000 ppm), of the air quality (0…100 % VOC), the temperature (–35...+80 °C) and the relative air humidity (0…100 % RH). International system of units SI (default) can be changed to imperial (via Modbus).
The following parameters can be accessed via the Modbus: Temperature, relative humidity, air quality (VOC), carbon dioxide (CO2) and atmospheric pressure. The sensor is used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being. One sensor for every 30 m² of space is recommended.
A long-term stable, digital humidity and temperature sensor guarantees exact measurement results. The CO2 measurement is performed using an optical NDIR sensor (non-dispersive infrared technology). The detection range is calibrated for standard applications such as monitoring residential rooms and conference rooms. The air quality is detected by a VOC sensor (mixed gas sensor for volatile organic substances). This sensor determines the loading of the room air due to contaminated gases such as cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions etc. With regard to the expected air contamination, low, medium or high VOC sensitivity can be selected.

Innovative Modbus sensor with galvanically separated RS485-Modbus-interface, selectable bus termination resistance, DIP switch for setting the bus parameters and bus address in current-free state, internal LEDs for telegram status display, two separate push-in terminals and large three-line display (illuminated; with customised programming in the 7-segment and dot-matrix range). The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 4.4 W/ 24 V DC typical; < 6.4 VA/ 24 V AC typical;
peak current 200 mA
Data points
temperature, relative humidity,
air quality (VOC), carbon dioxide (CO2),
atmospheric pressure
Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % RH (without dew formation)
Deviation of humidity
typical ± 2 % RH (20…80 % RH ); at + 25 °C, otherwise ± 3 %
Measuring range, temperature
–35...+80 °C
Operating range, temperature
–10...+60 °C
Units
switchable metric / imperial
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor, VOC
VOC sensor (metal oxide) with automatic calibration
(VOC = volatile organic compounds)
Measuring range, VOC
0...100 % air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches)
VOC sensitivity low, medium, high
Measuring accuracy, VOC
± 20 % of final value (referred to calibrating gas)
Service life
> 60 months (under normal load conditions)
depending on the type of loading and gas concentration
Measuring range, CO2
0...5000 ppm
Sensor, CO2
optical NDIR sensor (non-dispersive infra-red technology)
including atmospheric pressure compensation (up to 1100 mbar)
with automatic and manual calibration
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Response time
< 2 minutes
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Measuring range
0...5000 ppm
Measuring ranges
0...100 % Air quality - VOC sensitivities (low/medium/high)
0...5000 ppm
Ambient temperature
–10...+60 °C
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
4 s / 32 s
Process connection
by screws
Protective tube
stainless steel V2A (1.4301), Ø 16 mm, NL = 55 mm
Electrical connection
0.14 - 1.5 mm², via push-in terminal
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
2x M 16 x 1.5; including strain relief, exchangeable
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Protection type housing
IP 65
Standards
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014/ 30/ EU
Display
three-line display with illumination, cutout approx. 70 x 40 mm (W x H),
for displaying actual humidity, actual temperature, air quality and / or the actual CO2 content