Duct humidity, temperature and CO2 sensor KFTM-LQ-CO2-Modbus
temperature Temperature
temperature Luftfeuchtigkeit
temperature CO2
temperature VOC

Duct humidity, temperature, air quality and CO2 sensor AERASGARD® KFTM-LQ-CO2-Modbus

Item no. 1501-8118-6001-500
EAN 4251325624037
Product group: WG02

In Stock

Usually ships in 1 to 3 days
518,71 €
617,26 € incl. VAT + shipping
+

Description

Duct humidity, temperature, air quality and CO2 sensor AERASGARD® KFTM-LQ-CO2 - Modbus
Patented quality product (patent no. DE 10 2014 010 719.1)

Maintenance-free AERASGARD® KTM - CO2 - SD/ KFTM - CO2 - W duct air quality measuring transducer with active output, automatic calibration (fixed), in an impact resistant plastic housing with quick-locking screws, for determining the CO2 content of the air (0...2000 ppm/0...5000 ppm) and the temperature (–35...+80 °C). The transmitter converts the measured values into a standard signal of 0-10 V.

Maintenance-free AERASGARD® KFTM - LQ - CO2 - W duct air quality measuring transducer with active/switching output, automatic calibration (can be deactivated), in an impact resistant plastic housing with quick-locking screws, optionally with/without sisplay, for determining the CO2 content of the air (0...2000 ppm/0...5000 ppm), the quality in three VOC sensitivity levels (low/medium/high), the temperature (–35...+80 °C) as well as the relative air humidity (0…100% r.H.). The transmitter converts the measured values into a standard signal of 0-10 V or 4...20 mA (switchable).

These sensor devices are used in offices, hotels, convention centres, apartments, shops, etc. for the purpose of evaluating the indoor climate. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and improving well-being.

A long-term stable, digital humidity and temperature sensor guarantees precise measuring results.

The CO2 content is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range is calibrated for standard applications such as the monitoring of residential and conference rooms.
The air quality is detected by a VOC sensor (mixed gas sensor for volatile organic substances). This sensor determines the load of contaminated gases in the room air, such as from cigarette smoke, body perspiration, exhaled breathing air, solvent vapours, emissions from building components, etc. Low, medium or high VOC sensitivity can be selected depending on the expected air contamination.

Technical details

Voltage supply
24 V AC/ DC (± 10 %)
Power consumption
< 4.4 W/ 24 V DC typical; < 6.4 VA/ 24 V AC typical;
peak current 200 mA
Data points
temperature, relative humidity,
air quality (VOC), carbon dioxide (CO2),
atmospheric pressure
Measuring range, humidity
0...100 % RH
Operating range, humidity
0...95 % RH (without dew formation)
Deviation of humidity
typical ± 2 % RH (20…80 % RH ); at + 25 °C, otherwise ± 3 %
Measuring range, temperature
–35...+80 °C
Operating range, temperature
–10...+60 °C
Temperature deviation
typically ± 0.2 K at +25 °C
Sensor, VOC
VOC sensor (metal oxide) with automatic calibration
(VOC = volatile organic compounds)
Measuring range, VOC
0...100 % air quality; referred to calibrating gas;
multi-range switching (selectable via DIP switches)
VOC sensitivity low, medium, high
Measuring accuracy, VOC
± 20 % of final value (referred to calibrating gas)
Service life
> 60 months (under normal load conditions)
depending on the type of loading and gas concentration
Measuring range, CO2
0...5000 ppm
Sensor, CO2
optical NDIR sensor (non-dispersive infra-red technology)
including atmospheric pressure compensation (up to 1100 mbar)
with automatic and manual calibration
Measuring accuracy, CO2
typically ± 30 ppm ± 3 % of measured value
Temperature dependence, CO2
± 5 ppm/ °C or ± 0.5 % of measured value/ °C
(whichever is higher)
Pressure dependence
± 0,13 %/ mm Hg
Gas exchange
by diffusion
Response time
< 2 minutes
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Measuring range
0...5000 ppm
Measuring ranges
0...5000 ppm
0...100 % Air quality - VOC sensitivities (low/medium/high)
Ambient temperature
–10...+60 °C
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
4 s / 32 s
Process connection
by mounting flange, plastic
(included in the scope of delivery)
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection, Ø 20 mm, vmax = 30 m/s (air)
without filter: NL = 202.5 mm / with plastic filter: NL = 235 mm (optional with metal filter: NL = 227 mm)
Electrical connection
0.14 - 1.5 mm², via push-in terminal
Cable connection
cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector according to DIN EN 61076-2-101 (optional on request)
Housing
plastic, UV-stabilised,
material polyamide, 30 % glass-globe reinforced,
with quick-locking screws
(slotted/ Phillips head - combination),
colour traffic white (similar to RAL 9016)
Housing dimensions
126 x 90 x 50 mm (Tyr 2)
Cable gland
2x M 16 x 1.5; including strain relief, exchangeable
Long-term stability
< 2 % in 15 years
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529) housing only! (PLEUROFORM IP 30)
Protection type housing
IP 65