Duct humidity and temperature sensor KFTF - Modbus
temperature Temperature
temperature Luftfeuchtigkeit

Duct humidity and temperature sensor HYGRASGARD® KFTF-Modbus

Product group: WG01

In Stock

Usually ships in 1 to 3 days
209,13 €
248,86 € incl. VAT + shipping
+

Description

Duct humidity and temperature sensor HYGRASGARD® KFTF - Modbus
Quality product for the HVAC sector, accuracy ±3% or ± 2%
The measuring transducers are used in non-aggressive, dust-free environments, in refrigeration, air conditioning and cleanroom engineering, hotels, engineering rooms, meeting and conference facilities. They provide precise detection of temperature and humidity. A digital, long-term stable sensor is used as a measuring element for humidity and temperature. Fine adjustment by the user is possible. The sensor is suitable for ceiling and duct installation or for integration in equipment.

Technical details

Voltage supply
24 V AC (± 20 %) and
15…36 V DC
Power consumption
< 1,0 W/ 24 V DC
< 2,2 VA/ 24 V AC
Data points
Temperature [°C], relative humidity [% RH],
dew point [°C], absolute humidity [g / m3],
mixture ratio [g / kg], enthalpy [kJ / kg]
Measuring range, humidity
0...100 % RH
Measuring range, temperature
–35...+80 °C
Temperature deviation
typically ± 0.6 K at +25 °C
Measuring accuracy
± 2 %
Sensor
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
Sensor protection
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
Measuring range
0...100 % RH (humidity)
-35...+80 °C (temperature)
Measuring ranges
0...100 % RH
–35...+80 °C
Zero point offset
± 10 % RH (humidity)
± 5 °C (temperature)
Ambient temperature
–30...+70 °C
Medium
clean air and
non-aggressive, non-combustible gases
Bus protocol
Modbus (RTU mode),
address range 0...247 selectable
Signal filtering
4 s / 32 s
Process connection
by mounting flange, plastic
(included in the scope of delivery)
Protective tube
PLEUROFORM, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 235 mm (optionally 100 mm), vmax = 30 m/s (air)
(option on request in stainless steel V2A (1.4301), Ø 16mm)
Cable gland
2x M 12 x 1.5 (Y-adapter); with strain relief,
exchangeable, max. inner diameter 6 mm
Long-term stability
± 1 % per year
Permissible air humidity
< 95 % RH, non-precipitating air
Protection class
III (according to EN 60 730)
Protection type
IP 65 (according to EN 60 529)*
Protection type housing
IP 65
Standards
CE conformity
according to EMC Directive 2014/ 30/ EU,
according to EN 61 326